Basic data required for a dimensioning
Humidification chamber isothermal
Humidification chamber isothermal
The results indicate the required humidification output [kg/h] to achieve a relative humidity of 50 %.
The values marked in green refer to the DIN winter case (DIN 1946) with an absolute moisture content of 1.4 g/kg.
Electrical connection dimensioning: approx. 750 W / kg steam output
Waste water dimensioning: Per steam cylinder up to 18 l / min